[{"data":1,"prerenderedAt":61},["ShallowReactive",2],{"q-105170-arch_construction-34":3},{"question":4,"neighbors":26,"sameNumber":45,"prev":34,"next":37},{"id":5,"classKey":6,"session":7,"year":8,"subject":9,"number":10,"groupStem":11,"ownStem":12,"stem":12,"options":13,"answer":18,"answerKind":20,"answerS":11,"answerNote":11,"images":21,"explanation":22,"withheld":11,"deepChars":23,"freq":24,"indexable":25},"arch-105170-801-0103-034","architect","105170",105,"建築構造與施工",34,null,"下列水平走向的建築水電管線：①強電 ②給水 ③排水 ④污水，自上到下的排列順序何者正確？",{"A":14,"B":15,"C":16,"D":17},"①②③④","①③④②","②③④①","②①③④",[19],"A","single",[],"本題考點：建築水電管線在同一路徑水平並行時的上下配置原則——電在水上、給水在排水之上、污染性最高的污水在最下方。\n【正解理由】管線上下排列的判斷標準有兩個：一是「漏了會害到誰」，二是「重力往哪裡流」。電力管線最怕水，若放在水管下方，水管接頭滲漏或管壁結露滴水會直接落在電纜與線槽上，造成漏電、短路，所以強電放在最上方。給水管輸送的是飲用水，最怕被污染；依《建築物給水排水設備設計技術規範》第 3.5.5 節，用戶給水管線與排水或污水管埋設於同一管溝時，給水管線之底部全段須高出排水或污水管最高點30公分以上，且接頭均須為水密性之構造並減至最少數，可見給水管的位置必須在排水管與污水管之上。排水（雨水與一般雜排水）與污水（含糞尿之排水）都靠重力流動，其中污水污染性最高、一旦滲漏影響最大，放在最下方，其他管線就不會位於它的下方承接滲漏。依此由上而下為強電、給水、排水、污水，即①②③④。故選 A。\n【逐項排除】\n(A) 正確，為本題答案。①強電在最上方避免受水害；②給水在排水、污水之上，避免被滲漏污染；③排水在④污水之上，污染性最高者墊底，四項排列都符合上述原則。\n(B) 錯誤。①③④② 把給水放在最下方，位於排水管與污水管之下，排水或污水管一旦滲漏，就會向下污染給水管，正好與《建築物給水排水設備設計技術規範》第 3.5.5 節要求給水管底部高於排水或污水管最高點的方向相反。強電在最上方這一點雖然正確，但要把②移到③④之上，排成①②③④才對。\n(C) 錯誤。②③④① 中給水、排水、污水三者的相對次序沒有錯，錯在把強電放在最下方，所有水管都位於電力管線上方，任何一條水管滲漏或結露滴水都會落在電纜與線槽上，有漏電、短路的危險。要把①移到最上方才對。\n(D) 錯誤。②①③④ 把給水放在強電之上；給水管是加壓輸送的管線，接頭滲漏時水會噴濺或滴落到下方的電力管線。排水在污水之上這部分正確，但①與②的上下位置要對調，排成①②③④才對。\n【記憶點】由上而下「電、給、排、污」：怕水的放最上，怕髒的放其次，最髒的放最下。",756,1,true,[27,30,33,36,39,42],{"number":28,"session":7,"stem":29},31,"在鋼構建築中，鋼梁與混凝土鋼浪板樓版之間如何結合？",{"number":31,"session":7,"stem":32},32,"下列有關鋼桁架的敘述，何者錯誤？",{"number":34,"session":7,"stem":35},33,"如下列參考圖示，有關隔震工法的敘述，何者錯誤？",{"number":37,"session":7,"stem":38},35,"下列那項門五金不具有支承門扇自重之功能？",{"number":40,"session":7,"stem":41},36,"下列那一個工程項目一般歸屬於假設工程？",{"number":43,"session":7,"stem":44},37,"有關電梯的敘述，下列何者錯誤？",[46,49,52,55,58],{"number":10,"session":47,"stem":48},"114180","為防止動力基樁等施工設備之倒塌，下列敘述何者錯誤？",{"number":10,"session":50,"stem":51},"113190","依營造安全衛生設施標準，任何型式之護欄，其杆柱及任何杆件之強度及錨錠，應使整個護欄具…",{"number":10,"session":53,"stem":54},"112190","外牆瓷磚採用非水泥砂漿類之黏著劑鋪貼後，如在一般標準環境下進行接著強度試驗，依據 C…",{"number":10,"session":56,"stem":57},"111180","下列何種裝修行為不屬於建築物室內裝修管理辦法之規範對象？",{"number":10,"session":59,"stem":60},"110180","俗稱「Masago」的油壓長壁挖掘機，是國內開挖連續壁最普遍應用的機具之一。下列敘述…",1791863214598]