[{"data":1,"prerenderedAt":59},["ShallowReactive",2],{"q-105170-arch_construction-52":3},{"question":4,"neighbors":24,"sameNumber":43,"prev":32,"next":35},{"id":5,"classKey":6,"session":7,"year":8,"subject":9,"number":10,"groupStem":11,"ownStem":12,"stem":12,"options":13,"answer":15,"answerKind":17,"answerS":11,"answerNote":11,"images":18,"explanation":20,"withheld":11,"deepChars":21,"freq":22,"indexable":23},"arch-105170-801-0103-052","architect","105170",105,"建築構造與施工",52,null,"下列四圖所示，何者為混凝土澆置施工造成的冷縫缺陷？",{"A":14,"B":14,"C":14,"D":14},"",[16],"D","single",[19],"\u002Fimages\u002Farch-105170-801-0103-052.png","本題考點：辨識混凝土澆置常見缺陷的外觀特徵，區分冷縫、蜂窩、鋼筋保護層不足等不同成因。\n【正解理由】冷縫是混凝土分次澆置時，先澆的混凝土已開始凝結，後澆的混凝土接上去卻無法與之結合成一體，在兩者之間留下的接合不良面。《結構混凝土施工規範》第 9.3.3 節指出混凝土澆置應視情況妥為分層、分段或分區澆置，以免形成冷縫，並說明施工縫若未妥善處理即為冷縫；同規範第 15.5.6 節也說明連續澆置可避免冷縫的產生。因此冷縫的外觀特徵是一條沿著「前後兩次澆置的交界」延伸的線狀接縫，而不是局部的孔洞或鋼筋外露。依題圖，(D) 在兩柱之間的牆面上出現一條由上方往下方斜向延伸、邊緣粗糙的長線，正是澆置時混凝土沿斜面流下堆積、前後層間隔過久，在先後兩層混凝土的交界形成的斜向接縫。故選 D。\n【逐項排除】\n(A) 不符合題目所問。圖示為牆或柱腳處一大片粗骨材裸露、鋼筋外露的缺損，屬「蜂窩」：骨材析離、砂漿流失或搗實不足，粗骨材之間沒有被砂漿填滿而形成空洞。它是局部的不密實區，不是兩次澆置之間的接縫。\n(B) 不符合題目所問。圖示表面多處混凝土缺損、可看到鋼筋網格，右側剖面中鋼筋緊貼構材表面，屬「鋼筋保護層不足、露筋」一類缺陷，成因在鋼筋位置或墊塊固定，與澆置先後的接合無關。\n(C) 不符合題目所問。圖示為牆底與樓板交接處的牆腳兩側出現粗骨材外露，屬牆腳處的蜂窩、漏漿：模板底部與既有樓板之間封模不密，砂漿由縫隙流失，牆腳只剩粗骨材。它雖然發生在兩次澆置的交接位置附近，但圖上呈現的是骨材外露的不密實，而不是先後兩層混凝土之間的接合面。\n(D) 符合題目所問。牆面上一條斜向貫穿的接縫，沿著先後澆置的混凝土交界延伸，是澆置中斷或間隔過久、未連續澆置所形成的冷縫。\n【記憶點】冷縫是一條「先後兩層混凝土接不起來的線」，蜂窩是一片「骨材之間沒填滿的洞」，露筋是「鋼筋跑到表面」，三者外觀不同、成因也不同。",679,1,true,[25,28,31,34,37,40],{"number":26,"session":7,"stem":27},49,"模板施工時，脫模劑之適當使用時機為何？",{"number":29,"session":7,"stem":30},50,"當建築物之柱牆與梁或樓版同時澆置混凝土時，須先澆置柱牆至少若干小時後，方可繼續澆置其…",{"number":32,"session":7,"stem":33},51,"「混凝土坍度」係指下列何者？",{"number":35,"session":7,"stem":36},53,"國內建築物外牆面材較少留設龜裂誘發縫，形成不規則裂縫修補困難，一般留設龜裂誘發縫之原…",{"number":38,"session":7,"stem":39},54,"地下連續壁兼作地下室外牆使用時，其防水處理下列何者正確？",{"number":41,"session":7,"stem":42},55,"依鋼筋混凝土工程設計規範，混凝土直接澆置於土壤或岩石上，其鋼筋保護層厚度最小為多少 …",[44,47,50,53,56],{"number":10,"session":45,"stem":46},"114180","依據建築技術規則有關牆板隔音之規定，下圖所示的輕隔間系統可用於何種空間之牆面？填充材…",{"number":10,"session":48,"stem":49},"113190","下列有關輕隔間詳圖之敘述，何者錯誤？矽利康填縫原結構體（鋼承板） 1.2 m加強橫柱…",{"number":10,"session":51,"stem":52},"112190","既有房屋結構進行結構耐震補強時，下列何者並非有效補強工法？",{"number":10,"session":54,"stem":55},"111180","下列樓梯扶手細部詳圖，何者不符合無障礙設計規範？",{"number":10,"session":57,"stem":58},"110180","下圖為某國小校園之透水鋪面詳圖，地坪材料為連鎖磚，其透水性能主要由磚與磚的乾砌間隙達…",1791863214746]