[{"data":1,"prerenderedAt":61},["ShallowReactive",2],{"q-105170-arch_environment-10":3},{"question":4,"neighbors":26,"sameNumber":45,"prev":34,"next":37},{"id":5,"classKey":6,"session":7,"year":8,"subject":9,"number":10,"groupStem":11,"ownStem":12,"stem":12,"options":13,"answer":18,"answerKind":20,"answerS":11,"answerNote":11,"images":21,"explanation":22,"withheld":11,"deepChars":23,"freq":24,"indexable":25},"arch-105170-801-0104-010","architect","105170",105,"建築環境控制",10,null,"醫院建築空調設計，下列何種空間須採取強制排氣以維持負壓？",{"A":14,"B":15,"C":16,"D":17},"X 光室","燙傷病房","開刀房","肺病病房",[19],"D","single",[],"本題考點：醫院空調的室壓（正壓、負壓）分區原理。室壓由送風量與排風量的相對大小決定：排風大於送風、以強制排氣把空氣往室內抽，就形成負壓，用來把室內污染「關在裡面」；送風大於排風形成正壓，用來把外界污染「擋在外面」。題目要找的是必須維持負壓的空間。\n【正解理由】肺病病房收治的是可經空氣（飛沫核）傳播的呼吸道傳染病患者，例如肺結核。病人咳嗽、說話時產生的病原微粒可長時間懸浮於空氣中，若病房對走廊是正壓或等壓，開門、人員進出時含菌空氣就會流向走廊與其他病房，造成院內感染。因此肺病病房要以強制排氣使排風量大於送風量，讓病房相對走廊維持負壓，空氣只會由走廊流入病房、再經排氣系統處理後排出，污染被限制在病房內。這個需求是「防止病原外洩」，與其他三個選項「保護室內病人或無空氣污染外洩疑慮」的需求方向相反，故選 D。\n【逐項排除】\n(A) 不符題目所問。X 光室的特殊管制對象是放射線，處理方式是牆體、門扇的遮蔽構造與安全連鎖，而不是氣流方向。依《建築技術規則建築設備編》第 15 條，X 光機或放射線之電氣裝置，每一組機器應裝設保護開關於該室之門上，當室門未緊閉時機器即自動斷電，室外門上並應裝設紅色及綠色標示燈；這些都是防止人員誤入受照射的措施。X 光室並無空氣傳染源要封鎖，一般空調即可，不需以強制排氣維持負壓。\n(B) 不符題目所問。燙傷病房的病人皮膚屏障大面積受損，最怕的是外界細菌入侵造成傷口感染，空調要保護的對象是「室內病人」。因此燙傷病房應維持正壓，並搭配高效率過濾的潔淨送風，讓空氣由病房往外流，阻止走廊的污染空氣進入。若改成負壓，反而會把外界含菌空氣吸進病房，方向完全相反。\n(C) 不符題目所問。開刀房要保持手術部位的無菌環境，同樣是「防外界污染入侵」，所以採正壓，並以潔淨度很高的送風由上而下推送，將手術區的微粒帶離，空氣由開刀房流向外側的清潔走廊與前室。開刀房內雖然也需要排除麻醉氣體，但整體室壓是正壓，不是以強制排氣維持負壓。\n(D) 符合題目所問，本題答案。肺病病房的空調目標是隔離空氣傳染源，必須以強制排氣讓排風量大於送風量，維持相對負壓，並搭配前室與獨立排氣，避免病原經由氣流擴散到其他區域。\n【記憶點】「怕被傳染的房間用正壓，會傳染別人的房間用負壓」：燙傷病房、開刀房正壓；肺病（空氣傳染）隔離病房負壓；X 光室防的是放射線，不靠室壓。",838,1,true,[27,30,33,36,39,42],{"number":28,"session":7,"stem":29},7,"通風塔（wind tower）起源於下列何種氣候區？",{"number":31,"session":7,"stem":32},8,"室內水蒸氣發生量為 1.5 kg\u002Fh，室外空氣絕對濕度為 0.005 kg\u002Fkg'，…",{"number":34,"session":7,"stem":35},9,"下列何者為風壓係數(Cp)的定義？（P 為壓力，△P 為壓力差，ρ 為空氣密度，U …",{"number":37,"session":7,"stem":38},11,"有關水體對環境影響之敘述，下列何者錯誤？",{"number":40,"session":7,"stem":41},12,"下列揮發性有機化合物，何者之沸點最低？",{"number":43,"session":7,"stem":44},13,"下列有關於日照時間的敘述，何者正確？",[46,49,52,55,58],{"number":10,"session":47,"stem":48},"114180","改善室內空氣品質的策略包括：①污染物源頭管理 ②通風換氣設計 ③空氣淨化設備使用 ④…",{"number":10,"session":50,"stem":51},"113190","有關聲學的計量方式「響度」（loudness）之相關敘述，下列何者錯誤？",{"number":10,"session":53,"stem":54},"112190","下列那一個物理指標與眩光程度的關係最密切？",{"number":10,"session":56,"stem":57},"111180","正午太陽直射光的色溫（K）與下列何者最為接近？",{"number":10,"session":59,"stem":60},"110180","依據建築技術規則中，有關避雷設備之導線與安裝規定，下列敘述何者錯誤？",1791863214127]