[{"data":1,"prerenderedAt":61},["ShallowReactive",2],{"q-107180-arch_environment-5":3},{"question":4,"neighbors":26,"sameNumber":45,"prev":34,"next":37},{"id":5,"classKey":6,"session":7,"year":8,"subject":9,"number":10,"groupStem":11,"ownStem":12,"stem":12,"options":13,"answer":18,"answerKind":20,"answerS":11,"answerNote":11,"images":21,"explanation":22,"withheld":11,"deepChars":23,"freq":24,"indexable":25},"arch-107180-801-0104-005","architect","107180",107,"建築環境控制",5,null,"在冷氣空調系統中，下列那個部位最容易產生結露現象？",{"A":14,"B":15,"C":16,"D":17},"室內出風口","室內回風口","風管內側表面","空氣濾網表面",[19],"A","single",[],"本題考點：冷氣空調系統中「結露」發生的位置判斷。結露的條件是：某個表面的溫度低於接觸它的空氣之露點溫度，空氣中的水蒸氣便在該表面凝結成水滴。\n【正解理由】冷氣運轉時，回風與外氣混合後通過冷卻盤管，被降溫到很低的溫度並同時除濕，離開盤管的送風溫度低、相對濕度接近飽和。這股冷風經風管送到室內出風口，出風口的葉片、框架與周邊天花板被冷風持續冷卻，表面溫度往往低於室內空氣的露點；而出風口外側正是溫度較高、含濕量較多的室內空氣，兩者在出風口表面相遇，水蒸氣就凝結成水珠，嚴重時沿出風口滴水，形成考生熟悉的「冷氣出風口滴水」現象。四個選項中，同時具備「低溫表面」與「接觸高濕的室內空氣」兩個條件的位置只有室內出風口，故選 A。\n【逐項排除】\n(A) 正確。出風口表面被低溫送風冷卻，外側接觸的卻是溫暖潮濕的室內空氣，表面溫度低於室內空氣露點的機會最大，是本題所問最容易結露的部位。室內濕度越高（例如梅雨季、人員密集或開門頻繁的空間），或送風溫度越低、風口周邊混合不良時，出風口結露越明顯。\n(B) 錯誤。回風口吸入的是室內空氣本身，風口表面溫度與室內氣溫相近，高於室內空氣的露點，缺少「表面比露點冷」這個要件，因此不易結露。回風口常見的問題是積塵，不是結露；容易結露的應是送風側的出風口。\n(C) 錯誤。風管內流動的就是送風本身，風管內側表面受管外環境加熱，溫度不會低於管內送風溫度，因此也不會低於送風的露點，內側表面缺乏結露條件。風管真正容易結露的部位是「外表面」：未保溫或保溫破損的冷風管，外表面被管內冷風冷卻，又接觸天花板內較潮濕的空氣，才會凝結水珠；所以冷風管的保溫要連同防潮層包覆在外側。把結露位置寫成「內側」，是把冷熱兩側的關係弄反了。\n(D) 錯誤。空氣濾網一般設在冷卻盤管上游，過濾的是尚未降溫的回風與外氣混合空氣，濾網表面溫度與這股空氣相近，不會低於它的露點，因此不易結露。濾網的主要課題是積塵造成阻力上升、風量下降，須定期清洗或更換。空調系統中刻意讓水分凝結的是冷卻盤管，凝結水由盤管下方的集水盤收集排出，並不在濾網。\n【記憶點】結露＝表面溫度低於「接觸空氣」的露點；冷風一側的出風口表面碰上暖濕室內空氣最易結露，風管則是外表面結露而非內側。",950,1,true,[27,30,33,36,39,42],{"number":28,"session":7,"stem":29},2,"下列相同厚度材料的隔熱性能，由隔熱佳至隔熱差之順序為何？①保麗龍 ②乾燥木板 ③混凝…",{"number":31,"session":7,"stem":32},3,"有關高性能綠建材中節能玻璃之敘述，下列何者錯誤？",{"number":34,"session":7,"stem":35},4,"有關市面上使用常溫水噴霧搭配風扇吹出之「冷風扇」，空氣吹出前後在濕空氣線圖上之變化為…",{"number":37,"session":7,"stem":38},6,"有關室內空氣污染來源，下列敘述何者錯誤？",{"number":40,"session":7,"stem":41},7,"二氧化碳是室內空氣的指標污染物，我國室內空氣品質管理法中對於二氧化碳的 8 小時平均…",{"number":43,"session":7,"stem":44},8,"室內採用高壓放電式空氣清淨機時，可能產生何種空氣污染物？",[46,49,52,55,58],{"number":10,"session":47,"stem":48},"114180","下列那個措施無法防止冬季時壁體表面結露的發生？",{"number":10,"session":50,"stem":51},"113190","下列何者是高層建築物設置中間水槽或減壓閥的給水壓力（kg\u002Fcm2）臨界標準？",{"number":10,"session":53,"stem":54},"112190","單層均質材料的隔音性能與面密度有關，在質量控制頻域下，依質量法則（Mass Law）…",{"number":10,"session":56,"stem":57},"111180","若屋頂版的面積為 100 m2，整體構造材料的熱傳透率 U 值為 0.6 kcal\u002F…",{"number":10,"session":59,"stem":60},"110180","下列空間或場所作業之照度需求，何者要求最高？",1791863211004]