[{"data":1,"prerenderedAt":62},["ShallowReactive",2],{"q-109180-arch_construction-46":3},{"question":4,"neighbors":27,"sameNumber":46,"prev":35,"next":38},{"id":5,"classKey":6,"session":7,"year":8,"subject":9,"number":10,"groupStem":11,"ownStem":12,"stem":12,"options":13,"answer":18,"answerKind":20,"answerS":11,"answerNote":11,"images":21,"explanation":23,"withheld":11,"deepChars":24,"freq":25,"indexable":26},"arch-109180-801-0103-046","architect","109180",109,"建築構造與施工",46,null,"水電配管穿越結構伸縮縫時，下圖那些正確？不鏽鋼配管伸縮縫蓋板吊掛螺桿伸縮接頭部甲吊掛螺桿伸縮接頭部匯流排匯流排轉換箱丁 XLPE電力電纜連接線接地端子接線盒乙吊掛螺桿伸縮縫蓋板可繞金屬導管吊掛螺桿伸縮縫蓋板戊匯流排線槽線槽丙",{"A":14,"B":15,"C":16,"D":17},"僅甲丁","僅乙丁","僅乙丁戊","僅甲乙丙",[19],"B","single",[22],"\u002Fimages\u002Farch-109180-801-0103-046.png","本題考點：水電配管、配線與匯流排跨越結構伸縮縫時，跨縫段必須能吸收縫兩側結構的相對位移，也就是「縫兩側各自固定、跨縫段可撓並留餘長」，不能以剛性管線一體貫通。\n【正解理由】伸縮縫把建築物切成可各自伸縮、沉陷與搖動的結構單元，縫兩側在溫度變化、不均勻沉陷與地震時會產生相對位移，方向不只沿管線軸向，也包括垂直與水平錯動。管線若剛性連續跨縫，這些位移會全部由管線承受，結果是管體拉斷或擠彎、接頭鬆脫、電纜絕緣破損、給水管漏水。《建築技術規則建築設計施工編》第 200 條對地下建築物間連接部份設置伸縮縫時，要求貫通之各管線應有足夠之強度及韌性以承受其不均勻之沈陷，原理相同：跨縫處的管線要「能動」。逐圖檢視：乙在伸縮接頭部兩側以吊掛螺桿各吊一只接線盒，兩盒之間以呈鬆弛彎曲的可繞金屬導管連接，並以連接線與接地端子維持跨縫的接地連續；丁在伸縮接頭部兩側以吊掛螺桿各吊一只匯流排轉換箱，把剛性的匯流排在縫兩側截斷，兩箱之間改以呈彎曲餘裕的 XLPE 電力電纜連接。兩者都是縫兩側分別固定、跨縫段可撓，可吸收相對位移。甲、丙、戊則都是以剛性的管、槽或匯流排一體跨縫。正確的是乙與丁，故選 B。\n【逐項排除】\n(A) 錯誤。丁正確，但甲錯誤：依題圖所示，甲的不鏽鋼配管埋設在樓板內，連續穿過伸縮縫，縫上只覆蓋伸縮縫蓋板。配管兩端被兩側樓板混凝土握裹固定，縫一開合或錯動，管體就被拉扯剪切；不鏽鋼只是耐蝕，並不提供可撓性；伸縮縫蓋板只遮蓋縫口，不會讓管線獲得位移空間。甲要成立，跨縫段須改為可撓或可伸縮的接續構件，且管線不宜被兩側混凝土同時鎖死。\n(B) 正確。乙以可繞金屬導管搭配兩側接線盒跨縫，丁以 XLPE 電力電纜搭配兩側匯流排轉換箱跨縫，兩者皆為「兩側固定、中段可撓並留餘長」的做法，能吸收伸縮縫的相對位移。\n(C) 錯誤。乙、丁正確，但多選了戊：依題圖所示，戊的匯流排以吊掛螺桿吊在樓板下，呈一直線連續跨越伸縮縫，跨縫處未見轉換箱或可撓連接段。匯流排是剛性導體，兩側吊掛點隨各自的結構單元移動時，匯流排本體與接頭會受拉、壓或剪，與丁的差別正是丁在縫兩側截斷匯流排並改以電纜跨接。\n(D) 錯誤。只有乙正確，甲、丙皆錯，且漏了正確的丁。甲錯誤理由見 (A)；丙依題圖所示，線槽以吊掛螺桿吊於縫兩側樓板下，呈連續一體跨越伸縮縫，跨縫處未見可撓或伸縮的接續構件，縫兩側相對位移會直接作用在線槽與吊掛點上。丙要成立，線槽須在縫處斷開，並以可吸收位移的接續構件連接。\n【記憶點】跨伸縮縫的管線看三件事：縫兩側各自固定、跨縫段可撓、留足餘長；剛性管、線槽、匯流排一體跨縫都不對。",870,1,true,[28,31,34,37,40,43],{"number":29,"session":7,"stem":30},43,"智慧建築中各項設施之整合管理以確保系統的可靠性、安全性、使用方便性，係屬下列何種指標…",{"number":32,"session":7,"stem":33},44,"下列擋土措施之敘述，何者錯誤？",{"number":35,"session":7,"stem":36},45,"地下室永久性擋土牆防水層之防水處理，下圖何者正確？",{"number":38,"session":7,"stem":39},47,"有一全開挖（open cut）工地，開挖深度為 8 公尺（含地下二層及筏基）尚未回填…",{"number":41,"session":7,"stem":42},48,"下列屋頂扶手欄杆施工細部，何者較能防止金屬欄杆銹蝕後導致外牆髒污？",{"number":44,"session":7,"stem":45},49,"下列窗臺細部詳圖，何者較容易造成室內漏水？",[47,50,53,56,59],{"number":10,"session":48,"stem":49},"114180","基礎工法中，有關預力混凝土樁（P.C 樁）與一般離心式鋼筋混凝土樁（R.C 樁）之比…",{"number":10,"session":51,"stem":52},"113190","鋼構造之高強度螺栓施工安裝，下列何項描述錯誤？",{"number":10,"session":54,"stem":55},"112190","依營造安全衛生設施標準規定，對於施工構臺應辦理項目，下列敘述何者錯誤？",{"number":10,"session":57,"stem":58},"111180","依據 CNS12642 公共兒童遊戲場設備適用範圍之規定，其使用者年齡範圍為：",{"number":10,"session":60,"stem":61},"110180","下列何者不是「高性能節能玻璃綠建材」規範範圍？",1791863206902]