[{"data":1,"prerenderedAt":61},["ShallowReactive",2],{"q-114180-arch_environment-28":3},{"question":4,"neighbors":26,"sameNumber":45,"prev":34,"next":37},{"id":5,"classKey":6,"session":7,"year":8,"subject":9,"number":10,"groupStem":11,"ownStem":12,"stem":12,"options":13,"answer":18,"answerKind":20,"answerS":11,"answerNote":11,"images":21,"explanation":22,"withheld":11,"deepChars":23,"freq":24,"indexable":25},"arch-114180-801-0104-028","architect","114180",114,"建築環境控制",28,null,"某房間面積 50 m2、室內高度 3 m，具有 2 扇可對流通風之窗戶，假設垂直於窗戶之穩定風速為 0.1 m\u002Fs，該房間的窗戶有效開口面積為多少 m2 時，恰好能達成每小時換氣次數 3 次？",{"A":14,"B":15,"C":16,"D":17},"0.63","1.25","2.50","5.00",[19],"B","single",[],"本題考點：自然通風的換氣量計算：所需換氣量 Q = 換氣次數 × 室容積，再以 Q = 有效開口面積 × 風速，反求所需的有效開口面積。\n【正解理由】先由每小時換氣次數求出每小時所需換氣量，換成每秒的流量後，除以垂直於窗戶的風速，即得有效開口面積。室容積 = 50 m² × 3 m = 150 m³；所需換氣量 = 3 次\u002Fh × 150 m³ = 450 m³\u002Fh = 0.125 m³\u002Fs；有效開口面積 = 0.125 m³\u002Fs ÷ 0.1 m\u002Fs = 1.25 m²，與 (B) 相符。故選 B。\n【逐項排除】\n(A) 不符合。0.63 m² 明顯小於所需的 1.25 m²，以此開口在 0.1 m\u002Fs 風速下的通風量不足以達成每小時 3 次換氣。\n(B) 符合。有效開口面積 1.25 m² 在 0.1 m\u002Fs 風速下，每秒通風 0.125 m³，每小時 450 m³，恰為 150 m³ 室容積的 3 倍。\n(C) 不符合。2.50 m² 是把正確的 1.25 m² 再乘以 2（誤把窗戶扇數當成倍數）所得，題目給的有效開口面積已是對流通風路徑的有效面積，不需要再乘扇數；以 2.50 m² 計，換氣次數會超過題目所求的恰好每小時 3 次。\n(D) 不符合。5.00 m² 遠大於所需的 1.25 m²，換氣次數會遠超過每小時 3 次，不是「恰好」達成的面積。\n【演算步驟】① 室容積：V = 面積 × 室高 = 50 m² × 3 m = 150 m³。② 每小時所需換氣量：Q = n × V = 3 次\u002Fh × 150 m³ = 450 m³\u002Fh。③ 換算成每秒：Q = 450 m³\u002Fh ÷ 3600 s\u002Fh = 0.125 m³\u002Fs。④ 有效開口面積：A = Q \u002F v = 0.125 m³\u002Fs ÷ 0.1 m\u002Fs = 1.25 m²。\n【記憶點】換氣量 = 換氣次數 × 室容積 = 有效開口面積 × 風速；時與秒的單位要先統一。",497,1,true,[27,30,33,36,39,42],{"number":28,"session":7,"stem":29},25,"消防設備提高建築物安全性能的方式，下列敘述何者錯誤？",{"number":31,"session":7,"stem":32},26,"一部冷氣機每小時可吸收 60,000 kcal 的熱量，大約相當於多少美國冷凍噸（U…",{"number":34,"session":7,"stem":35},27,"有關空調系統冰水主機能源效率分級標示圖，下列敘述何者錯誤？",{"number":37,"session":7,"stem":38},29,"關於建築物類型與其合理的空調容量（m2\u002FUSRT），下列何者最不合理？",{"number":40,"session":7,"stem":41},30,"某辦公建築於冷房期間，採用機械通風設備引入外氣時兼顧節能的控制方式，下列何者錯誤？",{"number":43,"session":7,"stem":44},31,"關於緊急用昇降機之設計注意事項，下列敘述何者錯誤？",[46,49,52,55,58],{"number":10,"session":47,"stem":48},"113190","有關新建建築物的電梯機廂無障礙設計，下列敘述何者錯誤？",{"number":10,"session":50,"stem":51},"112190","某棟 11 層集合住宅，2 至 11 樓為住戶樓層，每層樓有 5 戶住戶、每戶 4 …",{"number":10,"session":53,"stem":54},"111180","有關空調設備主要裝置之敘述，下列何者錯誤？",{"number":10,"session":56,"stem":57},"110180","設有滅火器之樓層，自樓面居室任一點至滅火器之步行距離最多應在多少公尺以下？",{"number":10,"session":59,"stem":60},"109180","空調節能在換氣系統方面之考量，下列何者錯誤？",1791863196863]