[{"data":1,"prerenderedAt":61},["ShallowReactive",2],{"q-115180-arch_environment-25":3},{"question":4,"neighbors":26,"sameNumber":45,"prev":34,"next":37},{"id":5,"classKey":6,"session":7,"year":8,"subject":9,"number":10,"groupStem":11,"ownStem":12,"stem":12,"options":13,"answer":18,"answerKind":20,"answerS":11,"answerNote":11,"images":21,"explanation":22,"withheld":11,"deepChars":23,"freq":24,"indexable":25},"arch-115180-801-0104-025","architect","115180",115,"建築環境控制",25,null,"建築與空調設備計畫整合概念上，下列何者較不適當？",{"A":14,"B":15,"C":16,"D":17},"熱源設備設置於屋頂","風管個機（FCU）設置於窗台室內側邊","全外氣空調箱懸吊於天花板內","冷卻塔設置於空曠密閉機房內",[19],"D","single",[],"本題考點：建築計畫與空調設備的整合配置，判斷熱源設備、風機盤管、外氣空調箱與冷卻塔各自應放在什麼位置，關鍵在各設備的散熱需求、負荷來源與維修空間。\n【正解理由】冷卻塔的功能是把冷凍機冷凝器排出的熱，藉由冷卻水與外氣接觸、部分水分蒸發而帶走，所以它的運轉前提是大量吸入新鮮外氣、並把濕熱空氣順暢排出。若把冷卻塔放在密閉的機房裡，排出的濕熱空氣無處可去，會被冷卻塔再度吸入（短路循環），進氣溫濕度越來越高，散熱能力隨之下降，冷凍機冷凝壓力上升、效率變差甚至跳機；水霧與濕氣也會滯留在室內。這與「空曠」兩字並不衝突：空間再大，只要是密閉的，外氣就無法流通。《建築技術規則建築設備編》第 99 條第 1 項所規範的情境正是冷卻塔設置在建築物屋頂上，並要求它與主要構造連接牢固，且為防震、防風及能抵禦其他水平外力的構造，屋頂正是外氣流通、可直接散熱的位置。題目問「較不適當」者，D 的配置違反冷卻塔的散熱原理，故選 D。\n【逐項排除】\n(A) 敘述正確。熱源設備（如氣冷式冰水機組、熱泵或與冷卻塔搭配的設備）放在屋頂，可以直接與外氣換熱、排熱路徑最短，又不佔用可出租或使用的樓層，運轉噪音與振動也遠離主要使用空間，是常見的整合做法。配合的條件是屋頂結構要承受設備重量、設備要做防振與固定，並保留維修動線。\n(B) 敘述正確。風機盤管機組（題目稱風管個機，FCU）放在窗台室內側，正好面對建築物外周區：日射得熱、玻璃的傳導熱與冬季冷輻射都集中在窗邊，把出風口設在這裡可以就近處理外周負荷，並抑制窗邊的冷氣流下沉與結露，是外周區的典型配置。\n(C) 敘述正確。全外氣空調箱負責把外氣處理後送入室內，體積較小的機型可以懸吊在天花板內，節省機房面積並縮短風管；配合的條件是吊架須固定在上方結構體、天花板要預留檢修口，並處理好振動與冷凝水排水。這是空間整合上可行的做法，不是錯誤配置。\n(D) 敘述錯誤，為本題答案。冷卻塔要靠外氣帶走蒸發的熱與水氣，設在密閉機房會造成濕熱空氣回流、散熱能力下降，與「空曠」與否無關。正確做法是把冷卻塔放在屋頂或外氣流通良好的開放位置，並與鄰近外氣口、排氣口保持距離，避免濕熱空氣再被吸入。\n【記憶點】冷卻塔一定要「見天」：它是靠外氣蒸發散熱的設備，放進密閉空間就等於關掉它的散熱口。",900,1,true,[27,30,33,36,39,42],{"number":28,"session":7,"stem":29},22,"根據建築技術規則，關於「火警探測設備」的敘述，下列何者正確？",{"number":31,"session":7,"stem":32},23,"空調機冷凍循環的過程中，冷媒所吸收之熱量會在那一個部位端進行熱交換後排出？",{"number":34,"session":7,"stem":35},24,"下列何者為空調壓縮式冷凍循環的過程？",{"number":37,"session":7,"stem":38},26,"關於空調系統計畫，下列何者錯誤？",{"number":40,"session":7,"stem":41},27,"中央式空調箱（Air Handling Unit, AHU）系統，下列何種建築類型最…",{"number":43,"session":7,"stem":44},28,"下列何者之空調換氣方式與其他三種空間不同？",[46,49,52,55,58],{"number":10,"session":47,"stem":48},"114180","消防設備提高建築物安全性能的方式，下列敘述何者錯誤？",{"number":10,"session":50,"stem":51},"113190","根據省水標章管理辦法，下列敘述何者錯誤？",{"number":10,"session":53,"stem":54},"112190","某建商將規劃雨水收集回收之量能，目前已知基地日降雨量為 6.5 mm\u002F日，可集雨面積…",{"number":10,"session":56,"stem":57},"111180","有關燃燒學說之燃燒四面體，下列何者錯誤？",{"number":10,"session":59,"stem":60},"110180","關於大便器的敘述，下列何者錯誤？",1795751977868]